Components / EMC Products / 3-Phase Block Filters / FMBC NEO
 
FMBC NEO

General Informations


FMBC NEO EMV 3-Phase Block Filter: 2-stage filter for 3-phase systems
Environment_Safety RoHS   Environment_Safety China-RoHS Approval marks cURus   Approval marks ENEC 10

Descriptions

Description

Terminals for three phases and ground
High symmetrical and asymmetrical attenuation
In the frequency range from 10kHz up to 300MHz

Standards

IEC 60939
UL 1283, Edition 5, CSA 22.2 No. 8-M1986, @ Ta 75 °C

Approvals

- VDE Certificate Number: 40029853
- UL File Number: E72928

Applications

Voltage rating 480 and 520 VAC for world wide acceptance
Protection against interference voltage from the mains
Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
Qualified for use in equipment according IEC/EN 60950

Weblinks

pdf, General Product Information , Approvals, RoHS , CHINA-RoHS , e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check PCN
top

Technical Data

Rated Current 7 - 180 A
Rated voltage 480 - 520 VAC, 50/60 Hz
Approval for 7 - 180 A @ 50 (75) °C / 480/520 VAC; 50/60 Hz
Overload Current 1.5 x Ir
Dielectric Strength for 480 VAC > 2.25 kVDC between L-L
> 2.75 kVDC between L-PE
Dielectric Strength for 520 VAC > 2.25 kVDC between L-L
> 2.75 kVDC between L-PE
Test voltage 2 sec
Number of Filter Stages 2
Weight 0.8 - 8 kg
Material: Housing Metal 
Sealing Compound UL 94V-0 
Mounting Screw-on mounting on chassis 
Terminal Screw clamps 
Operating Temperature [°C] -25 °C to 100 °C
Climatic Category 25/100/21 acc. to IEC 60068-1
Degree of Protection IP 20 acc. to IEC 60529
Protection Class Suitable for appliances with protection class 1 acc. to IEC 61140
MTBF > 200'000 h acc. to MIL-HB-217 F
top

Dimensions

Case 1U
FMBC_NEO_Massbild_Gehäuse_1U
1) Line
2) Load
Case 1C
FMBC_NEO_Massbild_Gehäuse_1C
1) Line
2) Load
Case 1Q
FMBC_NEO_Massbild_Gehäuse_1Q
1) Line
2) Load
Case 1R
FMBC_NEO_Massbild_Gehäuse_1R
1) Line
2) Load
Case 1S
FMBC_NEO_Massbild_Gehäuse_1S
1) Line
2) Load
Case 1F
FMBC_NEO_Massbild_Gehäuse_1F
1) Line
2) Load
Case 1G
FMBC_NEO_Massbild_Gehäuse_1G
1) Line
2) Load
Case 1V
FMBC_NEO_Massbild_Gehäuse_1V
1) Line
2) Load
top

CAD


Electrical Details

Diagrams

FMBC_NEO_Schaltbild
1) Line
top

Derating Curves

Permissible Working Current as a Function of Ambient Temperature
Admissible operating current in % of In
FMAD_FMAC_FMBC_FMBC-NEO_FMBD-NEO_Derating-Kurve
Ambient air temperature Ta °C

top

Technical data to the filter components

Rated Current  @ Ta 50°C (75°C)  [A] L [mH] L2 [μH] C1 [μF] C2 [μF] C3 [μF] R1 [MΩ] R2 [MΩ] R3 [MΩ] Filter-Type
7 (4.7) 2.7 5 3.3 3.3 3.3 - 1 1 Industrial Version
16 (12) 1.9 10 6.6 3.3 3.3 1 1 1 Industrial Version
30 (21) 1.9 10 6.8 3.3 3.3 1 1 1 Industrial Version
42 (31) 1.3 10 9.9 3.3 3.3 1 1 1 Industrial Version
55 (49) 1.8 13 10 3.3 3.3 1 1 1 Industrial Version
75 (52) 1.2 13 9.9 3.3 3.3 1 1 1 Industrial Version
100 (70) 1.2 13 9.9 3.3 3.3 1 1 1 Industrial Version
130 (92) 0.7 26 9.9 3.3 3.3 1 1 1 Industrial Version
180 (135) 0.4 31 10 3.3 3.3 1 1 1 Industrial Version
7 (4.7) 2.7 5 3.3 3.3 3.3 - 1 1 Industrial Version
16 (12) 1.9 10 6.6 3.3 3.3 1 1 1 Industrial Version
30 (21) 1.9 10 6.8 3.3 3.3 1 1 1 Industrial Version
42 (31) 1.3 10 9.9 3.3 3.3 1 1 1 Industrial Version
55 (49) 1.8 13 10 3.3 3.3 1 1 1 Industrial Version
75 (52) 1.2 13 9.9 3.3 3.3 1 1 1 Industrial Version
100 (70) 1.2 13 9.9 3.3 3.3 1 1 1 Industrial Version
130 (92) 0.7 26 9.9 3.3 3.3 1 1 1 Industrial Version
180 (135) 0.4 31 10 3.3 3.3 1 1 1 Industrial Version
top

Attenuation Loss

. . . . . 0.1/100Ω differential mode ........... 100/0.1Ω differential mode     - - - - differential mode   _____ common mode

Industrial Version

7A
FMBC_NEO_Einfügungsdämpfung_7A
16A
FMBC_NEO_Einfügungsdämpfung_16A
30A
FMBC_NEO_Einfügungsdämpfung_30A
42A
FMBC_NEO_Einfügungsdämpfung_42A
55A
FMBC_NEO_Einfügungsdämpfung_55A
75 A
FMBC_NEO_Einfügungsdämpfung_75A
100A
FMBC_NEO_Einfügungsdämpfung_100A
130A
FMBC_NEO_Einfügungsdämpfung_130A
180A
FMBC_NEO_Einfügungsdämpfung_180A
top

Variants

Table of variants

Rated Current  @ Ta 50°C (75°C)  [A] Rated Voltage [VAC] Tripped Power Dissipation [W] Leakage Current [mA] 1) Contact Resistance [mΩ] Weight [kg] Screw clamps [mm2] 2) Housing Packaging unit Order Number ABC-Code [?] MOQ [?] PU [?] e-Shop [?] SCHURTER Stock Check [?] Distributor Stock Check [?]
         
7 (4.7) 480 1.4 < 33 9.2 0.8 6 1U 3 FMBC-A91U-0710  A  1 3 » » »
16 (12) 480 4.9 < 33 6.3 1.1 6 1C 3 FMBC-A91C-1610  A  1 3 » » »
30 (21) 480 6.8 < 33 2.5 1.5 10 1Q 4 FMBC-A91Q-3010  A  1 4 » » »
42 (31) 480 13.8 < 33 2.6 1.9 10 1R 3 FMBC-A91R-4210  A  1 3 » » »
55 (49) 480 12.7 < 33 1.4 2.5 25 1S 2 FMBC-A91S-5510 1 2 » » »
75 (52) 480 16.9 < 33 1 3.8 25 1F 1 FMBC-A91F-7510 1 1 » » »
100 (70) 480 24 < 33 0.8 5 50 1G 1 FMBC-A91G-J010  A  1 1 » » »
130 (92) 480 30.5 < 33 0.6 4.8 50 1G 1 FMBC-A91G-J310  A  1 1 » » »
180 (135) 480 19.5 < 33 0.2 8 95 1V 1 FMBC-A91V-J810 1 1 » » »
7 (4.7) 520 1.4 < 33 9.2 0.8 6 1U 3 FMBC-A91U-0712 1 3 » » »
16 (12) 520 4.9 < 33 6.3 1.1 6 1C 3 FMBC-A91C-1612 1 3 » » »
30 (21) 520 6.8 < 33 2.5 1.5 10 1Q 4 FMBC-A91Q-3012 1 4 » » »
42 (31) 520 13.8 < 33 2.6 1.9 10 1R 3 FMBC-A91R-4212  A  1 3 » » »
55 (49) 520 12.7 < 33 1.4 2.5 25 1S 2 FMBC-A91S-5512  A  1 2 » » »
75 (52) 520 16.9 < 33 1 3.8 25 1F 1 FMBC-A91F-7512 1 1 » » »
100 (70) 520 24 < 33 0.8 5 50 1G 1 FMBC-A91G-J012  A  1 1 » » »
130 (92) 520 30.5 < 33 0.6 4.8 50 1G 1 FMBC-A91G-J312 1 1 » » »
180 (135) 520 19.5 < 33 0.2 8 95 1V 1 FMBC-A91V-J812 1 1 » » »
1) Worst case leakage current acc. to IEC60950 - Annex G4 (situation with two interrupted lines). Nominal leakage current acc. to IEC60950 - 5.2.5. can be found in section technical data.
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information www.schurter.com/emc_info
top