Components / EMC Products / General Product Information

General Product Information


The general product information contains detailed information on product approvals, code requirements, technical details, usage instructions and detailed test conditions.


Summary

Product standard / Comments on definitions used / CE Marking / Conformity to component standards / National approvals / Protection

Product standard – equipment standard Top

The product standard only contains minimum requirements. Attention is drawn to the fact that appliance specifications might contain requirements additional to or deviating from those specified in the relevant product standards.

Comments on definitions used Top

Please be aware that the specifications nominal value used in the German part of the Schurter catalogue and the data sheets, is synonymous with rated value.

The difference between these two values is a pure matter of definition. In order to avoid any unnecessary complications we will continue to use the specifications nominal value.

CE marking acc. to EU-directives Top

CE marking is the only marking which indicates that a product conforms to the relevant EU-directive.

CE Selbsteklaration

This means that the CE-mark is no quality or standard conformity mark but only an administration mark.

SCHURTER products are covered by the low voltage directives 72/23/EEC and 93/68/EEC. Those are valid for equipment and appliances with rated voltage values between AC 50 V to AC 1000 V as well as DC 75 V to DC 1500 V.

The CE marking of SCHURTER parts will be found on the label of the smallest packing unit. On request we will submitt a CE conformity statement for each component. CE conformity statements and approvals can also be retrieved from the internet under www.schurter.com.

Conformity to component standards, national approvals Top

National testing institutions are testing according to national and international standards or other generally recognized rules of technology. Their certification/approval-marks confirm the observance of the safety requirements which electric appliances must fulfil.

Approvals

ENEC 10      European Norms
Electrical Certification
VDE   VDE Verband Deutscher Elektrotechniker
VDE_Fertigungs (Certificate of conformity with factory surveillance)
UMF_Prüfzeichen   UMF  
cURus (Recognition) UL Underwriters' Laboratories (USA, Canada)
cULus_Prüfzeichen (Listing) UL Underwriters' Laboratories (USA, Canada)
UR (Recognition) UL Underwriters' Laboratories (USA)
UL (Listing) UL Underwriters' Laboratories (USA, Canada)
CSA_Acceptance   CSA Canadian Standard Association, Component Acceptance Service
CSA   CSA Canadian Standard Association
China   CCC China Compulsory Certification
PSE_Prüfzeichen   PSE Japan Electrical Safety & Environment technology Laboratories
KTL_Prüfzeichen   KTL Korea Testing Laboratory
TÜV   TÜV Technischer Überwachungsverein
NF   NF Norme française
NNO_Prüfzeichen   NNO Numéro de nomenclature Otan (OTAN = NATO = North Atlantic Treaty Organisation)
GAMT1_Prüfzeichen   GAM T1 Liste interarmées AIR MER TERRE de composants électroniques
SEV   SEV Schweizerischer Elektrotechnischer Verein
BSI_klein.eps   BSI British Standard Institute
SEMKO   SEMKO Svenska Elektriska Materielkontrollanstalten
N.eps   NEMKO Norges Elektriske Materiellkontroll
D.tif   DEMKO Danmarks Elektriske Materielkontrol
FI.eps   FIMKO Finnish Electrical Inspectorate
OVE.eps   ÖVE Österreichischer Verband für Elektrotechnik
KEMA_KEUR   KEMA Keuring van Elektrotechnische Materialien
IMQ.eps   IMQ Instituto italiano del marchio di qualità

National approvals

In addition to the combined UL/CSA approvals, most of the SCHURTER components are also approved by one of the European certification bodies like VDE (Germany), Electrosuisse (Switzerland) or SEMKO (Sweden). The safety testing of all these European certification bodies are based on the commen European safety standards. With the harmonisation effort in Europe, the different national European certification bodies have lost their importance and SCHURTER has decided to maintain only one European approval (e.g. VDE, SEV or SEMKO) in future. The others will not be renewed once they have expired.

Because UL and CSA are not members of the CENELEC, the standards of UL and CSA are not harmonised yet with the European standards. However, UL and CSA are trying to harmonize their standards with each other. Where possible, SCHURTER will apply for the combined cULus or cURus approval.

Further to development in Asia, SCHURTER has obtained national approvals from China, Japan and Korea.

Information about approvals

SCHURTER products are certified according to EN / IEC standards and carry country specific approvals in Europe.

SEV BSI_klein.eps SEMKO N.eps D.tif

VDE FI.eps OVE.eps KEMA_KEUR IMQ.eps

During the last few years European countries made much effort to reduce their approval marks to one generally accepted mark. The ENEC approval mark replaces (wherever possible) the previous approval mark. The ENEC mark is offered by all national certification bodies that signed for the European certification agreement (CCA)*.

SCHURTER decided to reduce the variety of European approval marks. For new approbations of SCHURTER parts only the ENEC will be mentioned in the future:

ENEC 10

Approvals for the US and Canada are according to the UL and CSA standards:

UL CSA

As UL and CSA are not a member of CENELEC these two are not according to the European approval marks. Wherever possible SCHURTER want to acquire the combined cULus approval mark:

cULus_Prüfzeichen

Since Aug. 1st. 2003 the Chinese approval mark is required for a lot of products to import to China. SCHURTER strives to get the approvals for the concerned products. For not testable products we offer an import certificate (free of CCC).

China

Further information:

http://www.enec.com

Approval Industry Links

* members of ENEC agreement:

01

AENOR

Spain

02

CEBEC

Belgium

03

IMQ

Italy

04

CERTIF

Portugal

05

KEMA

Netherlands

06

NSAI

Ireland

07

SEE

Luxembourg

08

LCIE

France

09

ELOT

Greece

10

VDE

Germany

11

OVE

Austria

12

BSI

Great Britain

13

SEV

Switzerland

14

SEMKO

Sweden

15

DEMKO

Danmark

16

FIMKO

Finland

17

NEMKO

Norway

18

MEEI

Hungary

19

BEAB

Great Britain

20

ASTA

Great Britain

21

EZU

Czech Republic

22

SIQ

Slovenia

23

-

-

24

TÜV

Rheinland

25

TÜV

PS

IP degrees of protection provided by enclosures (IP code) Top

Standards IEC 60529; EN 60529 and DIN 40050

Scope

These standards apply to the classification of degrees of protection provided by enclosures for electrical equipment with a rated voltage not exceeding 72.5 kV.

Object

The object of these standards is to give:

a) Definitions for degrees of protection provided by enclosures of electrical equipment as regards:

1. Protection of persons against access to hazardous parts inside the enclosure

2. Protection of the equipment inside the enclosure against ingress of solid foreign objects

3. Protection of the equipment inside the enclosure against harmful effects due to the ingress of water.

b) Designations for these degrees of protection.

c) Requirements for each designation.

d) Tests to be performed to verify that the enclosure meets the requirements of these standards.

Designations

The degree of protection provided by an enclosure is indicated by the IP code.

Elements of the IP code and their meanings

A brief description of the IP code elements is given in the following table.

IP xy

Meaning for the protection of equipment

Meaning for the protection of persons

 

Against ingress of solid foreign objectif

Against access to hazardous parts with

x = 0

(non protected)

(non protected)

x = 1

50 mm diameter

back of hand

x = 2

12.5 mm diameter

finger

x = 3

2.5 mm diameter

tool

x = 4

1.0 mm diameter

wire

x = 5

dust protected

wire

x = 6

dust tight

wire

     
 

Against ingress of water with harmful effects

 

y = 0

(non protected)

 

y = 1

vertically dripping

 

y = 2

dripping (15° tilted)

 

y = 3

spraying

 

y = 4

splashing

 

y = 5

jetting

 

y = 6

powerful jetting

 

y = 7

temporary immersion

 

y = 8

continuous immersion

 

y = 9K

high pressure, i.e. steam jet cleaning

 
Protection against electric shock Top

1. Protection against direct and indirect contact – general terms

The protection against electric shock on electric equipment as well as their components are divided into the following parts:

Protection against direct contact with live parts concerns all measures for the protection of human beings and animals against hazards which result from direct contact with live parts of electric equipment and their components.
Protection against indirect contact is the protection of human beings and animals against hazards which result from contact of live parts 1) of electric equipment as well as components thereof, which have become live due to an insulation failure.

1) Accessible, conductive part, which is not conductive normally but which may be conductive due to a failure.

2. Protection against direct contact with live parts e.g. of a fuseholder

The data sheets of the relevant components inform about the taken measures.

3. Protection against indirect contact

Measures for the protection against indirect contact on electrical equipment are defined according to IEC 61140 by the 4 protection classes 0, I, II, III. Each protection class includes two protection measures. Even if one of these measures should fail, no electric shocks will occur.

Protection class

Main protective measures

0

1. Basic insulation between live parts and accessible conductive parts.

2. Earth-free location, non-conducting environment.

I


Berührungsschutz Symbol Schutzklasse 1

1. Basic insulation between live parts and accessible conductive parts.

2. Means are provided for the connection of accessible conductive parts of the equipment to the protective (earthing) conductor in the fixed wiring of the installation in such a way that accessible conductive parts cannot become live in the event of a failure of the basic insulation.

II


Berührungsschutz Symbol Schutzklasse 2

1. Basic insulation between live parts and accessible conductive parts.

2. Additional insulation. Basic and supplementary insulation are summarised under the term “double insulation�?. Under certain circumstances also a “reinforced insulation» (single insulation system) may guarantee an equivalent protection against electric shock as a “double-insulation�? does. No terminal for a protective conductor is allowable. A possibly existing protective conductor must not be connected and has to be insulated like any live part.

III


Berührungsschutz Symbol Schutzklasse 3

1. Functional insulation.

2. Supply at safety extra-low voltage SELV (the circuit is isolated from the mains supply by such means as a safety isolating transformer). The protection against electric shock is in this case completely based on the supplying by SELV-circuits (U ≤ 42 V). Higher voltages are not generated in the equipment. No terminal for a protective conductor is allowable.

Power entry modules with filter

Same requirements are valid for filters as for RF suppression chokes.

Industrial mains filters

Frequency range 0.01 MHz ... 1000 MHz

General information Top

Electromagnetic compatibility (EMC) is the capability of electrical equipment (installations, devices, assemblies) to operate effectively in its electromagnetic environment (Immunity), without in turn irresponsibly affecting this environment (Emission).

Mains filters of various types are used for the protection of electronic circuits, components and equipment against transients or similar interference, on the mains power supply. A suitable filter can be selected from the existing product range for each equipment type in accordance with electromagnetic conditions of its environment.

Mains interference can be classified into four categories:

A) Fluctuations in the industrial mains supply
(magnetic voltage stabilizer)
B) Harmonic wave interference in the frequency range 100 Hz ... 2 kHz
(filter type selective harmonic)
C) Transient interference signals in the frequency range up to
300 MHz (filter type low-pass)
D) Sinusoidal interference signals in the frequency range up to
1 GHz (filter type broad band, low-pass)

In practice, however, interference is mainly found in the last three categories B, C and D. Superimposed on the high-voltage mains supply, such interference can affect the performance of electronic circuits, or even cause them damage. An optimally-designed mains filter can perform a double function:

Netzfilter Bild 1

Function 1

The filter protects an electronic control circuit from voltage spikes in the mains supply, which may be generated, for example, by electromechanical switches and relays.

Function 2

The same filter also acts simultaneously in the opposite direction. The HF interference generated in the unit by thyristor control is attenuated such that the boundary values Class B, (EN 55011/55022) are maintained.

Filters are usually made up of capacitors and inductance coils. Components such as leakage resistors, surge dissipators and VHF chokes can also be integrated into the filter. Broad band filters

which meet the highest requirements are often composed of 2 or 3 single stages put together to make one filter unit:

Leakage current according to IEC 60335-1

The leakage current of a device is mainly determined by the capacity value of the Y-capacitor.

According to international standards (IEC 60335-1) the following regulations with respect to leakage current can be assumed:

Type of appliance

Protection class

IL max. [mA]

U[V]

f[Hz]

Portable appliances

I

0.75

250

50

Stationary motor appliances *

I

3.5

250

50

Stationary heating appliances

I

0.75/kW (max. 5.0)

250

50

Appliances

II

0.25

250

50

Appliances

I, 0I, III

0.5

250

50

* Stationary appliances fixed or weighing in excess of 18 kg (without carrying handle).

Ref.

Laboratory

Medical

IT

Test equipment

UL

0.5 mA

(UL 1262)

0.1 mA

(UL 544)

3.5 mA

(UL 1950)

5.0 mA

(UL 1244)

IEC

0.1 mA

(IEC 60601-1)

3.5 mA

(IEC 60950)

3.5 mA

(IEC 61010-1)

Rated voltage UR (Umax)

The rated voltage UR is the maximum RMS alternating line to line voltage (Umax) which may be applied continuosly to the terminals of the filter. The rated voltage is the nominal voltage including 10% tolerances.

Example:

Filter with UR = 440 VAC is made for a power system with nominal voltage 400 VAC +10%.

For standard three phase filters the voltage between phase and earth is intended UR/√3 (example 440/250 VAC).

Filters made for IT power systems withstand a voltage between phase and earth equal to UR.

SCHURTER filters for IT systems have code endingwith „I“: ex. FMAC-0932-2512I.

The line frequency fN (50/60 Hz) may be exceeded under certain conditions. We recommend the users to consult in any case our technical department. DC power operation is possible in most cases.

Power distribution system

There are three main types of power distribution systems according to IEC 60950 (1.2.12): TN, TT, IT.

The TN POWER SYSTEM is a power distribution system having one point directly earthed, the exposed conductive parts of the installation being connected to that point by protective earth conductors. Three types of TN POWER SYSTEMS are recognized according to the arrangement of neutral and protective earth conductors: TN-S, TN-C-S, TN-C.

Example of a TN-C-S system

Filterparameter Beispiel TN-CS System

TN-C-S is in a system which neutral and protective functions are combined in a single conductors in a part of the system.

Example of a TT system

Filterparameter Beispiel TT System

A TT POWER SYSTEM is a power distribution system having one point directly earthed, the exposed conductive parts of the installation being connected to earth electrodes electrically indipendent of the earth electrodes of the power system.

Example of a IT system

Filterparameter Beispiel IT System

The IT POWER SYSTEM is a power distribution system having no direct connection to earth, the exposed conductive parts of the electrical installation being earthed. In this case the voltage between phase and earth can reach the line to line voltage.

Nominal Current IN

The technical data gives the max continuous supply current in function of the ambient temperature IN/νa. The SCHURTER range generally differentiates between two types of filters:

- High-current filter: νa at IN = 40°C
νamax = 100°C
- All other filters: νa at IN = 40°C
νamax = 85°C

The permissible working current at higher ambient temperatures can be read from the following graph.

Permissible working current as a function of ambient temperature

Up to the approved nominal ambient temperature a the filter can be operated continuously at its nominal current. Above this temperature the square of the nominal current drops off linearly and reaches its zero point at Tmax (85 or 100 °C).

Derating curve (approx.)

Netzfilter Derating Kurve angenähert

Formula:

zulässiger Nennstrom

I = admissible operating current at elevated ambient air temperature
In = rated current
Tmax = max. allowable ambient air temperature Ta (85 °C)
Ta = ambient air temperature
Tn = allowable ambient air temperature at rated current (40 °C)

Leakage current

(see also chapter RF suppression capacitors: General information) 1-Phase measuring techniques

Measurment method Top

Measurement of the leakage current (simplified).

The leakage current is measured from every pole of the network:

- to all accessible metal parts
- to metal parts of protection class II equipment which is separated
only by the base material from parts under voltage.

The test is made with AC at 250 V / 50 Hz.

Measurements are made in both switch positions (see diagram).

Netzfilter 1-Phasen Messmethode

Protection class l

Devices are fitted with a special grounding conductor to provide protection against electrical shocks (L,N,PE wire cable). SCHURTER filters correspond to protection class I.

Insertion loss acc. CISPR 17 (common- and differential mode)

Asymmetrical measurement

CISPR_17_Asymmetrisch_Alternate

In common mode measurements, the line and neutral conductors are measured with respect to earth.

Line (L) and neutral (N) are measured to earth (E).

Symmetrical measurement

CISPR_17_Symmetrisch

In differential mode measurements, the insertion transmission loss is measured between line and neutral through a balancing transformer; the earth wire is not used.

4-pole network with integrated balancing transformer for the measurement of insertion transmission loss in the symmetric case.

Measurement method

The insertion loss D is defined as that loss which results when a four-pole network is inserted into an existing layout, having a surge impedance Z, assuming that the LHS and the RHS terminal impedances of the four-pole network are equal in magnitude and real, the insertion transmission loss and the overall loss are the same.

The insertion transmission loss, in decibels, can be obtained as follows:

Einfügungsdämpfung in Dezibel

Insertion loss “alternate test method�?

Asymmetrical measurement

CISPR_17_Asymmetrisch_Alternate

Symmetrical measurement

Symmetrisch_Alternate

The alternate test method allows the measurement in the GHz frequency range whereas the CISPR 17 method does not cover frequencies above 30MHz. The insertion loss is measured in a throughput method (common mode) and a cross coupled method (differential mode). The differential mode measurement of the alternate test method is not directly comparable to the conventional measurement acc. CISPR 17.

Voltage tests on noise suppression filters complying to EN 133200 II Top

Nominal voltage

connections

Between

Inner and outer insulation

   

C*≤ 1 μF

C*> 1 μF

150 ≤ UR ≤ 250 VAC

4.3 UR VDC

1500 VAC or 2250 VDC

4.3 UR VDC

250 ≤ UR ≤ 500 VAC

4.3 UR VDC

2 kVAC or 3 kVDC

4.3 UR VDC

500 ≤ UR ≤ 760 VAC

4.3 UR VDC

3 kVAC or 4 kVDC

4.3 UR VDC

*) C is the capacity measured between the connection block to

which the high voltage is connected for test.

Nominal voltage

Between connection

Between connection and case

UR ≤ 250 VAC

1250 VAC or 1768 VDC

1500 VAC or 2121 VDC

In compliance to the known standards of the IEC, EN, VDE and UL, the filters are tested as follows. In principle, these tests correspond to those of the RF suppression capacitors.

Test duration

- 2 sec for production test

- 60 sec for types test

The SCHURTER final production test has a duration of 2 sec. This test may not be repeated more than one time (i.e. incoming inspection at the customer). Any filter that has been under test for 60 sec can not be commercially used (reduced life cycle).

Application classes (IEC 60068-1) Top

The aim of this standard is to create a basis for classification of telecommunication engineering electrical components according to application classes which correspond to their climatic and mechanical suitability.

Example:

Netzfilter Klimakategorie

* relative humidity

MTBF Top

The high reliability of the filters can be excelled from MTBF (meantime between failures). These values are according MIL-HB-217-F class GB at an amient temperatur 40§C at rated voltage and current.

3-stage filter Top

Netzfilter 3-Stufen-Filter

1st stage

A differential mode acting filter with high energy absorption. Discharging resistors are normally used for Cx capacitors > 100 nF. The capacitors are tested and approved as so-called class X noise suppression capacitors. The 1st stage serves as dl/dt limitation.

2nd stage

A common mode acting filter with a high, broad band attenuation ratio. A ZNR varistor surge serves as the overvoltage suppression component. The earthed capacitors are tested and approved as so-called class Y noise suppression capacitors.

3rd stage

Common mode as well as differential mode acting filter in the HF range up to 300 MHz. Feedthrough capacitors make high attenuation values possible up to the gigahertz range. These capacitors are also class Y type. SCHURTER uses only approved noise suppression capacitors according to EN 132400.

Filter assemblies Top

Three types of mains noise suppression filter assemblies are used in practice:

Collective suppressor

Netzfilter Sammelentstörung

The collective suppressor principle results in one filter per plant. This has to cope with the entire power input. In addition, all of the connecting cables have to be shielded. Furthermore interference generated by «A» device can reach other devices for instance «B» or «C» through the connecting cables. The following example promises to be a more economical solution. In many cases, the single suppressor principle is the most economical

solution.

Single suppressors

Netzfilter Einzelentstörung

Combined single and collective suppressor

From the technical point of view, only the combined application of both suppression techniques can result in a significant improvement.

Interference propagation Top

In the field of interference and RF suppression, the most significant means of transmission is the direct electrical connection, i.e. the connecting wiring. The radiation coupling is also important from the electromagnetic compatibility (EMC) point of view; it cannot, however, be dealt with here.

Interference propagation

Netzfilter Ausbreitung von Störungen

The capacitive and inductive coupling effects occur inside the case. These could be:

- Capacitive coupling through the coupling capacity of a mains transformer.
- Inductive coupling through control system wiring in parallel.

The introduction briefly mentioned the possibility of the mains filter operating with a double function. Depending on the main area of application, these filters are designated as either RF SUPPRESSION FILTERS or INTERFERENCE SUPPRESSION FILTERS.

The one filter may, therefore, appear under two references in the documentation. A filter is also classified by its mechanical design as well as its electrical data.

RF SUPPRESSION FILTERS impede the propagation of RF interference, generated by an electronic or electrical device into the mains. They also ensure an interference-free radio reception in the immediate vicinity.

INTERFERENCE SUPPRESSION FILTERS prevent mains interference from affecting electronic equipment. They enable an interference- free operation even in the case of a power supply badly affected by mains interference.

It is common to operate the mains filter in both directions in the one piece of equipment, allowing it to fulfil its double function as both interference and RF suppression filters as specified.

Common- and differential mode interference Top

Filter engineering differentiates between common and differential mode interference originating from supply lines.

Netzfilter assymmetr. und symmetr. Störung

In the case of a non-earthed interference source, interference at first only propagates along the connecting lines. Like the mains AC current, the parasitic current flows to the user on one lead, and returns to the interference source on the other. Both these currents are in differential mode. This type of interference is therefore referred to as differential mode interference.

Due to the mechanical configuration and its parasitic capacitance, parasitic currents are also generated in the earthing circuit. This parasitic current flows on both connecting leads to the user and over an earthed lead back to the interference source. Both currents on the connecting lead are in common mode. This type of interference is therefore referred to as common mode interference.

Filter classification Top

For easy reading of the catalogue data, SCHURTER uses the following simplified filter classification:

Attenuation value

Standard

Medium

High

Excellent

20-50 dB

40-70 dB

60-80 dB

70-95 dB

Operating leakage current

Medical

Standard

Industrial

Other

<0.1 mA

<0.5 mA

<5 mA

>5 mA

Medical filter

SCHURTER medical filters comply with UL544 and IEC 60601-1 standard specifications and are available in two versions, which differ in terms of their leakage current values.

Medical filter (M5)

Netzfilter Medical Filter (M5)

1) Line

2) Load

Medical filter (M80)

Netzfilter Medical Filter (M80)

1) Line

2) Load

Standard medical filters for direct person contact supplied by SCHURTER have a leakage current value of <5 μA (M5). This can only be achieved without Cy. Here, a common mode fault current against earth is not attenuated and the filter acts only on differential mode fault currents. In addition, an inlet in protection class II can be used here, as no earth connection exists. However, if an earth connection is desired, Type (M80) can be used for indirect person contact; this has a leakage current of <80 μA which is below the required limit value of 0.1 mA. Type (M80) is manufactured to special order.

Bleed resistor

Medical filters and filters with a X-capacitor >100 nF have a bleed resistor so that no inadmissible rest voltage occurs at the touchable pins of the inlet.

Chokes

RF suppression chokes conforming to IEC60938 Top

All SCHURTER filters are fitted with chokes which satisfy the guidelines set down by international and national standards organizations.

The most important test data for RF suppression chokes are:

Maximum variation

of –30% / +50% for compensated
inductance: –15% / +15% for linear and storage
Testfrequency 1MHz ± 20% at L 10 μH
100kHz ± 20% at 10 μH < L 1 mH
10kHz ± 20% at 1 mH < L 50 mH
50 to 120 Hz ± 20% at L > 50 mH
Testcurrent: 0.1 mA
Testtemperature: 25°C ± 3°C

Insulation resistance Ris: 6000 MΩ

Chokes for

Between connections

Inner and outer insulation

AC

4.3 UR VDC

2 UR + 1500 VAC, but at least 2000 VAC

DC

3 UR VDC

2 UR + 1500 VDC

Temperature rise at nominal current: ΔT = 60°C

Short-circuit strength:

EN and VDE: not applicable

SEV→: 25 x IN (2 half-waves)

Current compensated chokes in interference suppression filters Top

Netzfilter Funkentstördrosseln Var. 2

The main type of choke used in suppression filter engineering is the current compensated choke. This mainly damps the common mode interference. The differential mode parasitic current, or rather the magnetic flux they produce in the core, is compensated by means of a special type of winding. The relatively small attenuation of the differential mode parasitic currents can be balanced through the large, symmetrically connected capacitance Cx between the lines. Only the leakage inductance Ls of the choke is then of any importance.

Streuinduktivität LS (Drossel)

The high nominal inductance LN active for common mode parasitic currents allows the insertion of small, earthed capacitances CY in a filter circuit. These capacitances are regulated by international standards for leakage currents.

RF suppression capacitors: General information Top

All SCHURTER filters are fitted with class X or Y RF suppression capacitors in accordance with international standards (IEC, EN). These are mainly self-healing metallized paper or polyester types, tested against the standards of major countries around the world and approved as noise suppression capacitors. Class X capacitors are capacitors with unlimited capacity for those applications in which a failure caused by a short circuit cannot result in a dangerous electrical shock. Class Y capacitors are capacitors intended for an operating voltage Ueff = 250 V with increased electrical and mechanical safety and limited capacitance.

RF Suppression capacitor complying with IEC 60384-14 Top

All SCHURTER filters are equipped with components which have been tested and approved as RF suppression capacitors.

The most important test data for RF suppression capacitors are:

Capacitance Cx, Cy ± 20% for fM = 1 kHz

Insulation resistance Ris between the capacitor terminals:

for C > 0.33 μF: Ris x C > 2000 s (time constant)

for C 0.33 μF: Ris> 6000 MOhm

Country

Standard

C

Rigidity

Pulse Test 1.2/50 μs

Europe

EN 132400

X1

4.3 UR VAC

4.0 kV

 

IEC 60384-14.2

X2

4.3 UR VAC

2.5 kV

   

Y1

4.0 kVAC

8.0 kV

   

Y2

2.5 kVAC

5.0 kV

 

IEC 60950

X1

2700 VDC, 60s

4.0 kV

 

(Equipment Standard)

X2

2121 VDC, 60s

2.5 kV

         

USA

UL 1414

 

2121 VDC, 60s

50 Pulse,

10 kV,

1000 W

 

UL 1283

 

2121 VDC, 60s

2545 VDC, 1s

-

         

Switzerland

SEV 1055

x

4.3 UR VAC

3.0 kV

   

y

2(100 + 2 UR)

min. 2250 VAC

5.0 kV

X2Y® filter Top

X2Y® filter combines the X and Y capacitors into a component that is in contact with the filter enclosure over a broad surface. The leads connecting the capacitors are thereby eliminated and parasitic impedances are reduced to a minimum. This results in broadband suppression into high frequency ranges.

EMC requirements in Europe

Household, Luminaries and Telecommunication

Residential, commercial and light industrial

Class Industrial

(ISM) Industrial, Scientific and Medical

Emission

– IEC 61000-6-3 (EN 50081-1)

Emission

– IEC 61000-6-4(EN 50081-2)

– EN 55022 ITE Information technology equipment

– EN 55014 Household Applications and Tools

– Harmonic (IEC 61000-3-2)

– Voltage fluctuations (IEC 61000-3-3)

– EN 55011

– Harmonics (IEC 61000-3-2)

– Voltage fluctuation (IEC 61000-3-3)

Immunity

– IEC 61000-6-1 (EN 50082-1)

– IEC 61000-4-2 ESD

– IEC 61000-4-3 HF-Field

– IEC 61000-4-4 Burst

– IEC 61000-4-5 Surge

Immunity

– IEC 61000-6-2 (EN 50082-2)

– IEC 61000-4-2 ESD

– IEC 61000-4-3 Inducted HF-Field (enclosure)

– IEC 61000-4-6 Inducted HF-Field (lines)

– IEC 61000-4-4 Burst

– IEC 61000-4-5 Surge

– IEC 61000-4-8 NF Magnetic Field (only for magnetic devices)

Electrical safety regulations Top

The most important safety standards for equipment/installations are listed in the following:

IEC 60950 Safety of information technology equipment including electrical business equipment
IEC 60335 Safety of household and similar electrical appliances
IEC 61010-1 Safety requirements for electronic measuring appartus
IEC 60601 Safety requirements for electro-medical equipment
UL 1950 Safety requirements for information technology equipment
UL 544 Electric medical and dental equipment
Interference emissions Top

There are basically 2 types of emitted disturbances: conducted and radiated. Line interferences are high frequency noise signals which are superimposed on the useful signals on input and output lines. Interference signals can be of common- or differential mode type. The significance of line interference is reduced dramatically above a frequency of 30 MHz. From here radiated interference increases greatly. On the following pages we will nevertheless deal with conducted interference only.

Measuring technique CISPR 3 Top

Netzfilter Messmethode VDE 0871

Radio frequency interference boundary values Top

RFI testing station

Netzfilter Messplatz Funkentstörspannung

EN 55011: Boundary values and measuring systems for RF suppression for industrial, scientific and medical high frequency equipment (ISM), 1991 (see also CISPR 11 or VDE 0871)

Boundary values complying with EN 55011

Netzfilter Grenzwerte EN 55011

Quasipeak (QP) and Average (AV) are two limits, neither of which must be exceeded and which are measured by two different test receivers. The test arrangement remains the same. These boundary values replace the boundary values given by the old standards for broadband and narrowband noise generators.

Boundary values are divided into class A and B.

Into class A fall those devices which should not be operated in residential buildings and should not be connected to power supplies which also supply these areas. Class A boundary values shall not be exceeded.

Into class B fall devices for which above restrictions do not apply. Class B boundary values shall not be exceeded.

EN 55022: Boundary values and measuring systems for RF suppression for information technology installations (Telecommunications) 1987 (see also CISPR 22 or VDE 0878).

Boundary values complying with EN 55022

Netzfilter Grenzwerte EN 55022

Into class A fall all units which should be used in a commercial environment and should be used with a safety distance of 30 m to other units.

Into class B fall all units which have no restrictions on their use.

EN 55013: Boundary value and measuring techniques for RF suppression characteristics of radio receivers and connected applications.

EN 55014: Boundary values and measuring systems for RF suppression for electrical household appliances, handheld electrical tools and similar electrical products, 1993 (see also CISPR 14).

EN 55015: Boundary values and measuring systems for RF suppression for fluorescent lamps and lighting, 1993 (see also CISPR 13).

Harmonics Top

(EN 61000-3-2, IEC 61000-3-2)

Current harmonics represent a distortion of the normal sine wave provided by the utility. When a product such as an SCR switched load or a switching power supply distorts the current, harmonics at multiples of the power line frequency are generated. Two significant consequences arise as a result of harmonic generation. First, because of finite impedances of power lines, voltage variations are generated that other equipment on the line must tolerate. Second, when generated in a three-phase system, harmonics may cause overheating of neutral lines.

Power line harmonics are generated when a load draws a non linear current from a sinusoidal voltage. The harmonic component is an element of a Fourier series which can be used to define any periodic waveshape. The harmonic order or number is the integral number defined by the ratio of the frequency of the harmonic to the fundamental frequency (e.g., 150 Hz is the third harmonic of 50 Hz; n = 150/50).

After multiple postponement finishes at 1.1. 2001 the transition-period for the EN 61000-3-2, frequently called “PFC-Norm�?. It applies to all electrical and electronic devices with input current up to max. 16 A per phase, which are designed to connect to the general lowvoltage mains. Limits are set only for 220/380 V, 230/400 V and 240/415 V at 50 Hz.

This standard distinguishes four classes of equipment.

A Simmetric three phase equipment and all other equipment not in other classes

B Portable tools
C Lighting equipment
D Equipment having special waveshape (see EN 61000-3-2, paragraph 4 picture 1)

A harmonics test to conform to the standards must include an analysis of the incoming current up to the 40th harmonic (for fN = 50 Hz, fH = 2 kHz).

The IEC 61642 "Industrial a.c. networks affected by harmonics- application of filters and shunt capacitors" give guidance for the use of passive a.c. harmonic filters and shunt capacitors for the limitation of harmonics and power factor correction intended to be used in industrial applications, at low and high voltages.

Voltage fluctuations (Flicker) Top

(EN61000-3-3, IEC 61000-3-3, IEC 61000-3-5)

The appearance of flicker effects and voltage fluctuations on the mains supply is caused by varying loads connected to the mains. The most critical are the effects of voltage fluctuations on equipment such as lights and illumination. Here the light output and thereby the intensity is an exponential function of the supplied voltage. This fluctuation in light intensity is called flicker. Many people experience dizziness and headaches as a result.

There are various limit values depending on the type of voltage fluctuation (square, sinusoidal and mixed or erratic voltage fluctuation).

Flickers are measured by so-called flicker meters (arranged in compliance with EN 60808).

Immunity Top

ESD (Electrostatic Discharge)

(EN 61000-4-2, IEC 61000-4-2)

One of the main interference sources, along with switching through radio interference, is electrostatic discharge from people and equipment.

Burst

(EN 61000-4-4, IEC 61000-4-4)

One of the most common and most dangerous sources of interference are transient disturbances such as those originating from switching transients (interruption of inductive loads, relay contact bounce, etc.). The burst test measures the resistance of the device to repetitive fast transients.

Surge

(EN 61000-4-5, IEC 61000-4-5)

This test procedure measures the behaviour of a device when subjected to high-energy pulses. Sources of such pulses are switching events due to lightning strikes, short-circuits, or switching cycles which vary in time and place. Surge test on SCHURTER filters are according to EN 133200.

Specification of the burst test impulse

Netzfilter Burst Prüfimpulse IEC 1000-4-4

Surge voltage form in open circuit

Netzfilter Surge Spannungsform Leerlauf

Class

Relative ambient

humidity as low as [%]

Antistatic material

(floor)

Synthetic material

(floor)

Level air discharge

(kV)

Level contact discharge

(kV)

Class 1

35

x

 

2.00

2.00

Class 2

10

x

 

4.00

4.00

Class 3

50

 

x

8.00

6.00

Class 4

10

 

x

15.00

8.00

Test levels

The installation is characterized by following attributes

Voltage peak: [kV]

 

Repetition rate [kHz]

   

Power supply

Signal ports

 

Level 1

Well-protected

environment

- Suppression of all EFT/B* in the switched power supply circuits

- Separation between power supply lines and control and measurement circuits

- Shielded power supply cables with the screens earthed at both ends

0.50

0.25

5.0

Level 2

Protected

environment

- Partial suppression of EFT/B* in the power supply and control circuits

- Separation of all the circuits from other circuits associated with environments of higher severity levels

- Physical separation of unshielded power supply and control cable from signal and communication cables

1.00

0.50

5.0

Level 3

Typical industrial

environment

- No suppression of EFT/B* in the power supply and control circuits

- Poor separation of the industrial circuits from other circuits

- Dedicated cables for power supply, control, signal and communication lines

- Poor separation between power supply, control, signal and communication cables

2.00

1.00

5.0

Level 4

Severe industrial

environment

- No Suppression of EFT/B* in the power supply and control and power circuits

- No separation between power supply, control, signal and communication cables

- Use of multicore cables in common for control and signal lines

4.00

2.00

2.5

*EFT/B: Electrical Fast Transient/Burst

Class

Environment definition

Voltage peak [kV]

   

L → N [2kΩ]

L/N → PE [12Ω]

Class 0

well-protected

environment

- All cables with overvoltage protection

- Well-designed earthing system

- Surge voltage may not exceed 25 V

-

-

Class 1

Partly protected

environment

- All cables with overvoltage protection, well interconnected earth line network

- Power supply completely separated from the other equipment

- Surge voltage may not exceed 500 V

-

0.50

Class 2

- Separate earth line to earthing system

- The power supply is separated from other circuits

- Non-protected circuits are in the installation, but well separated and in restricted numbers

- Surge voltage may not exceed 1000 V

0.50

1.00

Class 3

- The installation is earthed to the common earthing system

- Protected electronic equipment and less sensitive electric equipment on the same power supply network

- Unsuppressed inductive loads are in the installation

1.00

2.00

Class 4

- The installation is connected to the earthing system for the power installation

- Current in the kA range due to earth faults

- The power supply network can be the same for both the electronic and the electrical equipment

- Surge voltages may not exceed 2000 V

2.00

4.00

Class 5

- Electrical environment for electronic equipment connected to telecommunication cables

- The interference voltages can be extremely high

- All cables and lines are provided with overvoltage protection

dep. on the local power supply network

dep. on the local power supply network

Pulse transformers

Introduction Top

The application range of pulse transformers is very broad. In most cases, a signal or a control pulse must be transmitted between electrically isolated circuits. This problem exists in the activation of thyristors and triacs, or in the operation of FETs or IGBTs in highpower switching circuits. Another application involves electrical isolation in telephone switchboards and data transfer systems.

High insulation rating Top

When used in power electronics, the secondary side of pulse transformers is normally at a high voltage potential. This requires a high insulation strength for pulse transformers.

Complying with VDE 110 b, Part 1, the following test voltages between the primary and the secondary circuits are required for transformers of protection class I and choke coils, as a function of the working voltage:

Working Voltage

Test Voltage Uisol

[V]

[V]

250

1500

500

2500

1000

3000

Test voltage Uisol Top

The test voltage for SCHURTER pulse transformers depend on the type of winding and coating on the coil wire. Exact information concerning each type is available in the technical specifications. The test voltage is in each case considerably higher than that prescribed by VDE 110 b.

Partial discharge voltage Ue Top

Partial discharges during normal operation have little effect on the operation of the circuit, but can accelerate the ageing of the pulse transformer. The glow discharge and the intermittent voltages are at least 50% higher than the approved working voltages for all SCHURTER pulse transformers. This provides the best assurance against long-term damage.

Definition of the rise time Tr Top

Over the almost straight-line in the lower 2/3 of the rise curve, i.e. in the area where the semiconductor is triggered with certainty, we draw a line and measure the time from 10% to 90% of the overall pulse height.

Impustransformatoren Anstiegszeit

The measurement is made with the following circuit. The load resistance RL is given for each type.

Impustransformatoren Anstiegszeit Schema

For a turn ratio of 1:1, the test voltage is 10V;

For a turn ratio of 2:1, the test voltage is 20V, and so on.

Trigger current Iign Top

The maximum trigger current is a guide value. For a given current, the drop in voltage over the secondary winding resistance is smaller than one volt.

The voltage-time integral Us • tw Top

The voltage-time integral is the product of the pulse height and width, measured at half pulse height. The voltage-time area is measured on the secondary side during operation under no load.

Impustransformatoren Spannugszeitfläche

The voltage-time integral Us • Tw is measured according to the principle of the following circuit. The same voltages as used for measuring the rise time are used.

Impustransformatoren Spannugszeitfläche Schema

Primary and secondary inductances Lp, Ls Top

Primary and secondary inductances are measured with a low-power signal of 0.1 mA/10 kHz at 25°C. The tolerance is -30% / +50%. The measured value can also vary up to ± 25% under temperature variation in the range 0°C to 70°C.

Coupling capacity Cc Top

The coupling capacity is measured between the primary and one secondary winding. This value varies depending on the type of winding. Bifilar windings, designed for models with faster rise times, have higher coupling capacitances than the layer or selection windings.

In general, this value is not important with regards transmission properties. To guarantee effective interference protection from the control electronics, however, the smallest possible coupling capacity is desired.

Turn ratio N Top

In the given turn ratios, the first figure always refers to the primary winding. Hence a «1:1» pulse transformer has the same number of winding on both the primary and the secondary windings. The turn ratio «3:1:1» stands for one primary and two secondary windings with a transformation ratio of three to one between the primary and the secondary windings.

Impustransformatoren Windungsverhältnis 1

SCHURTER offers pulse transformers with other turn ratios than specified on the data sheets upon request.

Example of application

Impustransformatoren Example of application

Power transistor in pulse operation

General information Top

UL approbation

The plastic cases and the potting resin of all SCHURTER pulse transformers are fire resistant in compliance with UL 94 V-0.

∫Udt

Voltage-time integral (Us•Tw)

Tr

Pulse rise time

Pm

Power dissipation at ambient 50°C

P

Power dissipation at elevated temperature

ϑa

Ambient temperature

Iign

Trigger current

Cc

Coupling capacity

RL

Test load resistance (secondary)

Rp

Primary resistance

Rs

Secondary resistance

Lp

Primary inductance = Ls x N2

Ls

Secondary inductance

Ueff

Working voltage primary-secondary in VRMS

Uisol

Test voltage

N

Turns ratio

Code

I1) T2) N3) F4) - 05) 26) 357) - D18) 039)

1) Pulse transf.
2) T.. conventional
S.. SMD
3) N.. normal
R.. small rise time
4) A.. 1:1 / B.. 2:1/C.. 3:1
F.. 1:1:1 / H.. 3:1:1
5) Brandlabel SCHURTER
6) CK:1..≤10pF / 2..>10..≤100pF
7) Case code
8) Trigger current
9) Inductance

Driver modules

DC/DC converter module Top

The PSDM-0DN1-5040 module is a DC/DC power supply converter designed to provide a galvanic isolated, regulated and monitored power to IGBT and MOSFET drivers. The module requires an input voltage of 12VDC ± 10% and has dual outputs of 15V and –4V with a maximum supply current of 140 mA. This DC/DC module has a unique diagnostic output permitting the user to monitor the converter output voltage and thus to avoid damage to the power stages resulting from under voltages.

IGBT driver modules Top

The IGBT driver modules PSDM-0DO2-5040 and PSDM-0DT2-5020 were developed to drive IGBT or MOSFET power transistors in an easy, safe and reliable way. The modules have an internal turnoff circuit that protects the output power stage in the event of a short circuit. The PSDM has an isolated DC/DC converter with a 2.4W output power for the drive circuit supply. (see PSDM-0DN1-5040). Data is transfered by an optocoupler or a transformer.

Connection description

Treibermodule Anschluss Beschreibung Treibermodul Abb.2

fig. 1: PSDM

PIN1: VDC

A stabilised voltage supply between 10V and 15V with respect to GND.

PIN2: GND

GND is connected to the frame of the electronic power supply.

PIN3: VSM

This output refelects the output voltage of the DC/DC converter. When more current is needed at the output stage, the voltage across VSM decreases. When VSM reaches the value of the DC/DC

converter power supply, then the DC/DC converter has reached the maximum transfer current.

PIN4: VCS1

VCS1 is the isolated positive output power supply for the driver logic.

PIN5: SGND

SGND is the electrically isolated output ground from the DC/DC converter.

PIN6: VCS2

VCS2 is the isolated negative output power supply for the driver logic.

PIN7: VES

VES is the external power supply for the driver logic. VES is connected to VCS2 to turn off the MOSFET/IGBT connected to the module.

PIN8: KGND

KGND is the isolated Kelvin ground that is connected to SGND.

PIN9: VO

Output VO is the signal output for the IGBT gate drive. In order to permit the switching speed to be set independently during turn-on and turn-off, two gate resistors and a diode must be used

(for example, Rg1 = 22 Ω and Rg2 = 100 Ω).

Treibermodule Gate Treiber Abb.2

fig. 2: Gate Driver

PIN10: DPR

This connection is used to monitor the voltage drop across the turned-on current transistor, so as to provide protection against short circuits and overloading on the IGBT. This involves monitoring the collector voltage and turning off the power transistor if this voltage rises above a certain threshold value. The best method of detecting an excess threshold value is through the use of an external fast or super-fast high voltage diode D1 (for example 1N4937) and an internal comparitor. The PSDM has power transistor supervision, which monitors the collector voltage on the IGBT. Under normal operating conditions when the IGBT is turned on and saturated, the voltage across DPR is kept low. When the IGBT is no longer saturated or turned off, the internal current source (270 μA) will trip out the comparitor. The comparitor threshold value is typically 6.5 V (DPRth). Resistor RRV is required to protect the PSDM from reverse voltage transients and should not be larger than 1kΩ. The fault event is transferred to the output pin FLT by an internal optocoupler.

Treibermodule Leistungstransistorüberwachung Dpr Abb.3

fig. 3: Power transistor supervision Dpr

PIN11: ISEN

Input ISEN is required to check the supply current across Risen, serving thus as a protection against short circuits and overvoltages on the IGBT. An RC filter is used across pins 8 and 11 to attenuate any high frerquency noise. If an overcurrent (VISOC> 65 mV) takes place across RISEN, IGBT will be turned off by an internal circuit. The signal fault is reset when another impulse appears at the signal input VIN. In the event of a short circuit across the output (VISSC> 130 mV), inductance will be very small. Measured across resistor Risen, the short circuit signal is transfered by an internal optocoupler to the output pin FLT. If a short circuit is detected, the IGBT remains turned off until the next impulse (Vin).

Treibermodule Stromüberwachung Isen Abb.4

fig. 4: Fault current detection Isen

PIN12: FLT

The PSDM has an active fault output. This fault output is internally interfaced to an optocoupler. In a turned-on state, the current range of the optocoupler is between 10 to 20 mA, possessing a high impedance in the turned-off state. The integrated circuit is shown below.

Treibermodule Fehlerausgang Abb.5

fig. 5: Fault output

The FLT pin is only enabled when it is used together with a DPR or ISEN signal. Voltage VFLT can be taken from 5V to 15V with a resistor. The supply current permitted is 10mA. In the event of a fault, output FLT is switched to GND.

PIN13: VIN

This input has a SchmittTrigger characteristic. HIGH level turns the power transistor on, LOW turns it off.

PIN15: VDD

A stabilised voltage supply between 4.5V and 5.5V with respect to GND.

Application example: Power supply 0-15V (fig. 6)

With this circuitry example, an output voltage of 0-15V is generated at V0. The two functions fault current detection (ISEN) and power transistor supervision (DPR) are inactively switched for this application. With this, SGND is connected to ISEN, DPR, VES and KGND. If necessary, a seprate resistor can be connected between V0 and IGBT in order to optimize the turning on and off of the semi-conductor.

Application example: Power supply -4-15V (fig. 7)

With this circuitry example, an output voltage of -4-15V is generated at V0. The two functions fault current detection (ISEN) and power transistor supervision (DPR) are inactively switched for this application.

With this, SGND is connected to ISEN, DPR, VES and KGND. If necessary, a seprate resistor can be connected between V0 and IGBT in order to optimize the turning on and off of the semi-conductor.

Application example: Power transistor supervision (figure 8)

In this example, power transistor supervision is presented for the IGBTs. For this, output VCS2 (-4V) is connected to VES. Supervision is actively switched with the connection of VCS1 to ISEN. In addition, a high voltage diode is connected in series to a resistor between DPR and the IGBT collector. The capacitor is switched from DPR to SGND.

Application example: Fault current detection (figure 9)

With this example, a fault current detection circuitry is presented for the IGBTs. For this, output VCS2 (-4V) is connected to VES. A resistor RISEN is connected between ISEN and KGND. An RC filter is used to attenuate high frequency noise. A capacitor is needed between DPR and KGND.

Treibermodule Spannungsversorgung 0-15V Abb.6

fig. 6: Power supply 0-15V

Treibermodule Spannungsversorgung -4-15V Abb.7

fig. 7: Power supply -4-15V

Treibermodule Leistungstransistorüberwachung Abb.8

fig. 8: Power transistor supervision

Treibermodule Stromüberwachung Abb.9

fig. 9: Fault current detection

Automatic undervoltage turn-off

The PSDM module is equipped with undervoltage protection for the gate drive of the IGBT/MOSFET. Should the gate voltage be too low, the IGBT can quickly overheat; to avoid this, the undervoltage protection is arranged such that when the voltage drops below 10V, the gate voltage on the PSDM is turned off.

Layout and wiring (figure 10)

The driver module should be placed as close as possible to the power transistor so that the wiring is kept short. Long wiring connections should be avoided; it is recommended to twist the wires here.

Treibermodule Verdrahtung Abb.10

fig. 10: Wiring

New Products

> FMAC SINE DCL

SCHURTER expands its EMC output filter product portfolio, introducing 3-phase sine wave output  ...
Datasheet read more
> FMBC NEO

SCHURTER expands its filter product portfolio, introducing power line filter series FMBC NEO fo ...
Datasheet read more
> FMAC ECO

FMAC ECO / FMBC ECO – Cost optimized 3-phase line filters
Datasheet read more
> FMER SOL

 SCHURTER presents its new standard DC filter series FMER SOL suited for use on the DC side of  ...
Datasheet read more